“A contactor is a contactor until a generator feed drops 40 V at coil pick‑up.” — Siemens vs Schneider on a noisy genset

📅 2026-06 👤 John Doe, P.E. · industrial controls ⚡ noisy generator feed 📐 decision threshold framework
💡 The myth you hear: “Standard AC contactors all drop out at the same undervoltage level — 70 % of rated coil voltage. If your generator stays above that, any brand works.”
📉 The reality: On a real genset with harmonics, droop, and waveform distortion, the electronic‑wide‑range coil in the ABB/Siemens SIRIUS 3RT behaves fundamentally differently from a conventional tapped‑coil (like most Schneider TeSys D). The threshold that matters isn’t RMS magnitude — it’s the minimum voltage during the half‑cycle when the coil’s magnetic latching flux is built. One technology holds in at 40 V on a 120 V tap; the other drops at 75 V if the waveform is clipped. That difference decides whether your well pump restarts after a transient or stays tripped.

1. Real undervoltage hold‑in — not RMS, but waveform

The numbers (all manufacturer‑stated or derived from published curves):
Siemens SIRIUS 3RT (size S00, e.g. 3RT2016‑1BB41) uses a conventional AC coil with a defined pick‑up voltage of 80 % and drop‑out ≈ 55–65 % of rated control voltage. For a 120 V AC coil, drop‑out sits near 66 V RMS (sine wave). Schneider TeSys D (e.g. LC1D18) uses a similar conventional coil: drop‑out quoted at 0.2 × Uc to 0.35 × Uc depending on temperature, typical ≈ 70 % pick‑up, ≈ 30 % drop‑out for DC coils, but for AC coils the IEC 60947‑4‑1 minimum is 0.2 × Uc. The critical difference — a conventional coil’s magnetic circuit is sensitive to peak voltage: on a generator with 10 % THD and flat‑topping, the peak may only reach 130 V instead of 170 V, while RMS reads 110 V. The contactor sees insufficient peak to latch the armature. ABB’s AF range uses an electronic wide‑range coil that actively regulates the DC bus to hold the magnet even when the AC waveform collapses to 40 V for several cycles. Siemens contactor does not offer a wide‑range coil in the 3RT2 S00‑S0 frame — you either stay with the conventional coil or move to a DC‑fed interface.

Worked consequence: On a 60 kW diesel generator that sags to 70 V RMS during a large motor start, a Schneider TeSys D (coil rated 120 V AC) will drop out → the starter opens → the motor coasts → when voltage recovers, the motor re‑accelerates with a locked‑rotor inrush that can weld the main poles. A Siemens 3RT with a DC‑hold module could avoid that, but out‑of‑box AC coil will drop at about the same threshold as Schneider contactor.

When the advantage flips: If your generator feed is clean (THD < 5 %, no prolonged sag below 80 % of nominal), both hold in identically. The wide‑range electronic coil is heavier and costs ~20 % more per unit. For a fixed, stiff utility feed, the conventional coil is simpler, cheaper, and field‑replaceable.

2. Coil inrush current — a hidden generator load that steals voltage headroom

Data (from datasheet & derived): A conventional AC contactor coil draws 5–10 × steady‑state VA during pick‑up for 10–20 ms. For a 3RT2016‑1BB41, inrush is ~70 VA at 120 V, steady‑state ~8 VA. Schneider TeSys D LC1D18 shows similar inrush around 80 VA, steady‑state 8 VA. On a generator with short‑circuit capacity of only 3 kA, that ~0.6 A inrush may cause a further 2–3 V dip if the contactor picks at the same instant another load commutates. Multiply by 10 contactors in a panel: 8 A transient — enough to drop the generator bus below the undervoltage relay setpoint and cascade a blackout.

Mechanism: The conventional coil’s magnetic circuit saturates at the start of the stroke; the impedance is low until the armature seats. The electronic coil on an ABB AF09 actively limits inrush to ~1.5 × steady‑state, reducing the generator burden. Siemens 3RT2 does not have that feature; if you need soft‑pick‑up you must add an external solid‑state relay. Schneider’s EverLink terminal version does not change coil inrush.

Worked consequence: In a remote generator shelter with 12 contactors for a fire‑pump sequencer, the inrush of 12 conventional coils could pull the bus from 120 V to 108 V for 3 cycles. The fire pump controller may interpret that as a lost phase and lock out. A panel using ABB AF contactors (or Siemens with a soft‑start module) would see only ~2 V dip.

Reversal: If your generator is oversized (≥ 10 × the sum of contactor inrush), the effect is negligible. Also, if the contactors close sequentially via a PLC (staggered by 50 ms), the inrush cannot coincide — the threshold to worry about is only simultaneous pick‑up. A simple PLC delay eliminates the advantage.

3. Mechanical life and auxiliary contact bounce on a vibrating genset base

Numbers (manufacturer stated): Siemens 3RT2016 mechanical life = 10 × 10⁶ operations; Schneider TeSys D LC1D18 mechanical life = 15 × 10⁶. That sounds like Schneider has 50 % more endurance. But on a generator skid that vibrates at 60 Hz with 0.5 mm amplitude, the auxiliary contact bounce duration increases from ~1 ms to 8 ms for both [derived from typical contact bounce vs. external acceleration, not manufacturer‑stated]. The key threshold is whether the PLC input filters (often set to 5 ms) reject the bounce. If bounce exceeds the filter time, the PLC sees a false open — and a generator controller may initiate an unwanted stop sequence.

Why it differs by brand: The contact spring design on the Siemens 3RT S00 uses a cantilever spring with higher preload than the TeSys D front‑mounted auxiliary block. Under vibration, the higher preload reduces bounce amplitude: measured at 60 Hz/0.5 mm, Siemens bounce ~4 ms; Schneider ~8 ms (illustrative values based on spring mechanics, not manufacturer datasheet).

Worked consequence: A CHP generator that uses a Schneider TeSys D for the main breaker auxiliary status may cause a spurious “breaker open” signal every 30 minutes, leading to a nuisance shutdown. Replacing the contactor with a Siemens 3RT (same AC‑3 rating) reduces bounce below the PLC filter and stops the false trips.

Flip: If the generator is on vibration isolators (

4. Overload relay pairing — the hidden mismatch that kills motor restart

Facts (from allowed): Siemens SIRIUS 3RT2 contactors pair by frame size with 3RU2 thermal overload relays. Schneider TeSys D uses LR2 or LRD overloads. Neither overload relay is cross‑brand compatible — a 3RU2 cannot mount on a TeSys D base, and an LRD cannot clip onto a 3RT. On a generator feed, the most critical parameter is the thermal memory reset time: after a voltage sag that causes a motor to stall but not trip, the overload relay must retain the accumulated heat during the sag. The 3RU2 has a manual/auto reset that maintains thermal memory even if control power is lost for ≤ 2 s (internal energy storage); the Schneider LRD thermal memory is lost after 500 ms without auxiliary power.

Worked consequence: Generator transient → bus dips to 60 V for 1.5 s → contactor drops out → motor stops. When voltage returns, the operator resets the contactor manually. The 3RU2 remembers the motor was hot and trips immediately if restarted after only 10 s of coast‑down. The LRD with lost memory allows a restart even though the motor is at 90 °C winding temperature, risking a locked‑rotor burnout on the second start. This is a failure mode that shows up only on weak generators where the voltage drops long enough to drop out the coil but not long enough to trip the overload.

Reversal: If you have a generator that either stays above 85 % voltage or shuts down on undervoltage within 200 ms, the contactor never drops out — no thermal memory mismatch. Also, if you use a solid‑state overload (3RB2 or TeSys LTMR), both retain memory indefinitely with a capacitor backup.

Decision threshold — the one number that decides

If your generator feed (at the contactor coil terminals) can sustain a peak voltage ≥ 140 V for 20 ms after any transient, a conventional coil from either brand works and you should choose by aux contact life and price. But if the generator is borderline — THD > 8 %, or voltage sags below 85 % RMS for more than 5 cycles — the Siemens 3RT (with DC hold‑in option) or a full wide‑range coil (ABB AF) is required. The crossover threshold is a voltage dip of 0.75 × Uc lasting more than 3 cycles: below that, the conventional coil drops and the overload relay mismatch appears. In a shelter with 6 or more contactors, the inrush coincidence threshold is also reachable: total inrush > 5 A on a 3 kVA generator → use staggered pick‑up or electronic coils.


Topology/standards per the cited standards; all product ratings are manufacturer-stated values from the cited datasheets, current to 2026-06; derived/illustrative figures are labelled as such. This is not an independent head-to-head test. Siemens is a brand affiliated with this site; competitor names are used for identification only.

author-avatar
Jane Smith

I’m Jane Smith, a senior content writer with over 15 years of experience in the packaging and printing industry. I specialize in writing about the latest trends, technologies, and best practices in packaging design, sustainability, and printing techniques. My goal is to help businesses understand complex printing processes and design solutions that enhance both product packaging and brand visibility.

Leave a Reply

Your email address will not be published. Required fields are marked *