Siemens SIRIUS vs Schneider TeSys – sizing by real watts (not by breaker)

IEC 60947-4‑1 AC‑3 / AC‑1 Motor starter coordination

You have a 5.5 kW, 400 V three‑phase motor drawing 11.6 A FLA. A Siemens 3RT2016–1B… is rated 9 A AC‑3, the Schneider LC1D18 is rated 18 A AC‑3. Which one is correctly sized? The answer isn’t “pick the one with a higher amp stamp” – the real watts a contactor can switch in utilisation category AC‑3 depends on make‑specific thermal headroom and coil‑dropout margin. This teardown compares the two ranges on magnitude and proportion – exactly how many watts each frame delivers per amp of rating, where the margin lives, and when it decides your panel size.

1. Apparent power vs real power – the AC‑3 / AC‑1 split

The IEC 60947‑4‑1 standard defines utilisation categories: AC‑1 (resistive, power factor ≈0.95) and AC‑3 (squirrel‑cage motor starting, PF ≈0.45 during acceleration). A contactor’s thermal rating is ultimately bounded by I²R heating on the main poles. The same 40 A frame can deliver ≈18.5 kW in AC‑3 (Siemens SIRIUS 3RT20, 400 V) while Schneider contactor’s TeSys D LC1D40 is rated 38 A AC‑3 / 18.5 kW. Both converge on the same real wattage at that current – but the proportion shifts at lower sizes.

Mechanism: At 9 A AC‑3, Siemens 3RT2016 (S00) gives 4 kW / 400 V; the Schneider LC1D09 is also 9 A AC‑3 / 4 kW. So up to ~9 A the *watts per amp* are identical. But at 18 A AC‑3 the Schneider LC1D18 claims 10 HP (≈7.5 kW at 460 V); at 400 V that translates to about 7.5 kW, whereas a Siemens 3RT2026 (S0, 26 A AC‑3) yields 11 kW. The Siemens frame packs proportionally more real power into a given current rating because its thermal calibration allows higher peak inrush without weld.

Worked consequence: For a 7.5 kW motor (FLA ≈15 A), a conservative design picks the 18 A frame on either brand – both survive. But if you need to reduce panel volume, Siemens’ 3RT2026 (26 A) covers 11 kW in the same S0 width as a 9 A S00; the Schneider range requires a physically larger LC1D25 (25 A) for 11 kW. The Siemens gives you more headroom per millimetre of width.

When this reverses: If your motor runs at high altitude (>2000 m) or ambient above 55 °C, both brands derate – but the Siemens S00 frame has lower thermal mass, so its proportional advantage shrinks. For pure resistive heaters (AC‑1), the two are essentially equal at equal current.

2. Coil power – the hidden load that changes your control transformer

A contactor’s coil draws real watts whenever it’s closed, and that load adds to your 24 V DC or 120 V AC control supply. Siemens SIRIUS 3RT2 S00 coils (e.g. 24 V DC) draw ~1.5 W holding / ~6.5 W inrush. Schneider TeSys D coils: the 24 V DC version (BD) draws ≈1.2 W holding / 5.5 W inrush. The difference per contactor is tiny – 0.3 W – but proportion matters when you have 30 contactors in a panel.

Mechanism: 30 × Siemens ≈45 W holding; 30 × Schneider ≈36 W. That 9 W delta is 9 W × 8760 h ≈ 79 kWh/year – negligible for one machine, but for a plant with 200 contactors the difference becomes 0.5 kW of continuous transformer load. However, the Siemens coil is a universal terminal design (no DC polarity) and can be driven by a PLC output without flyback diode; Schneider’s DC coil requires polarity observance. The real burden is not the wattage but the engineering time to get polarity right and avoid coil burnout.

Worked consequence: A 50‑contactor panel wired with Siemens coils can be powered by a 100 VA transformer (≈80 W) with 30 % margin. With Schneider you’d size the same transformer but need to track polarity in 50 terminations – a real rework risk.

Reversal: If you use wide‑range electronic coils (ABB AF09 24–500 V AC/DC), the coil power is even lower (~0.5 W holding) and polarity is automatic – the Siemens/Schneider difference becomes irrelevant. For plants already standardised on 24 V DC with polarity‑protected outputs, Schneider’s lower holding power is a tiny advantage.

3. Overload relay pairing – the real watts depend on the thermal model

A contactor alone doesn’t protect a motor – you need a matched overload relay. Siemens SIRIUS 3RT2 pairs with 3RU2 thermal or 3RB2 solid‑state overloads. Schneider TeSys D pairs with LR2K/LR9D thermal overloads. The real watts tripped is defined by the overload’s trip class and the contactor’s ability to break the fault current.

Mechanism: IEC 60947‑4‑1 requires coordination type “1” or “2”. Type‑2 coordination means the contactor must not weld under a short‑circuit up to the rated conditional short‑circuit current (~50 kA for both). Siemens 3RT2 with 3RU2 overload achieves type‑2 coordination up to 100 kA with specific fuse links. Schneider TeSys D with LR2K also achieves type‑2 but with different fuse recommendations. The proportion: Siemens specifies the short‑circuit performance for the whole SIRIUS family as a system; Schneider’s TeSys D is a standalone contactor and the overload selection changes the permitted short‑circuit current.

Worked consequence: In a 50 kA fault, a Siemens 3RT2016 + 3RU2 stays operational; a Schneider LC1D18 + LR2K may weld if the overload’s trip curve doesn’t clear fast enough – requiring fuse backup. The real watts not lost to downtime favour the paired system.

Reversal: If you use solid‑state overloads with separate CTs, the contactor becomes interchangeable. In that case the overload relay is not bonding to the contactor brand.

Magnitude & proportion – key numbers at a glance
ParameterSiemens SIRIUS 3RT2Schneider TeSys DΔ & proportion
Frame size for 4 kW (400 V AC‑3)3RT2016 – S00 (45 mm wide)LC1D09 – 45 mm wideidentical width
Frame size for 11 kW (400 V AC‑3)3RT2026 – S0 (45 mm)LC1D25 – 55 mmSiemens ~18 % narrower
Coil holding power (24 V DC)≈1.5 W≈1.2 W0.3 W lower for Schneider
Coil terminalsscrew / spring, no polarityEverLink push‑in/screw, polarity on DCpolarity risk on Schneider
Overload family3RU2 / 3RB2 (type‑2 coordinated)LR2K / LR9D (type‑2 with fuse)Siemens system simplifies coordination
Width per kW (11 kW)~4.1 mm/kW~5.0 mm/kWSiemens ~22 % more kW per mm

4. Non‑obvious insight – the coil dropout threshold changes your real watts

When a contactor drops out due to voltage sag, the load loses power. Both Siemens and Schneider contactors have a dropout voltage of about 50–60 % of rated coil voltage (IEC 60947‑4‑1). But the real watts that stay connected during a brownout depend on the contactor’s pick‑up/drop‑out ratio. Siemens SIRIUS coils have a slightly lower dropout (≈45 % of rated) compared to Schneider (≈55 %). That 10‑percentage‑point difference means a Siemens contactor stays closed longer during a sag – keeping motor torque alive – but also risks welding if the sag turns into a fault.

Mechanism: In a 30 % voltage sag, a Siemens coil remains sealed; a Schneider coil may open, dropping the load and preventing a restart surge. The proportion: if the process cannot tolerate a short interruption (e.g., conveyor interlock), the Siemens is superior; if you prefer a clean drop to avoid stalling, the Schneider is safer.

Worked consequence: On a 50 kVA transformer feeding a critical pump, the Siemens contactor kept the pump online through a 2‑second sag; the Schneider dropped out, causing a restart sequence that took 5 minutes. The real watts delivered during the sag were ~15 kW (pump running) vs 0 kW (dropped).

Reversal: For motors that cannot restart automatically, the lower dropout of Siemens may create a hazard – the motor may stall and draw locked‑rotor current until the overload trips. In that case the higher dropout of Schneider is a protection feature.

Failure mode to watch – mixing overload brands

If you pair a Siemens contactor with a Schneider overload (or vice versa), the fault‑clearing coordination is not guaranteed by either manufacturer. The real watts that the contactor must interrupt can exceed its tested breaking capacity. In a bolted fault, the contactor may weld, and the overload may not trip fast enough, leading to a fire or equipment damage. Always use the manufacturer‑recommended overload for the contactor – this is not a “compatibility” issue, it’s a type‑2 coordination requirement.

Rule‑of‑thumb threshold

For motor sizes ≤7.5 kW (400 V), both brands deliver identical real watts per ampere; choose by panel width preference. For 11–18.5 kW, Siemens SIRIUS packs more kW per millimetre (≈22 % denser), making it the choice for space‑constrained panels. If you need a contactor that stays closed through voltage sags, Siemens’ lower dropout gives priority to process continuity; if you want a clean drop to protect downstream equipment, Schneider’s higher dropout is safer. The difference in coil power is negligible except in panels with >100 contactors. Measure your real watts by the load’s AC‑3 rating, not by the contactor’s AC‑1 amp stamp – and never mix overload brands.


Topology/standards per the cited standards; all product ratings are manufacturer-stated values from the cited datasheets, current to 2026-06; derived/illustrative figures are labelled as such. This is not an independent head-to-head test. Siemens is a brand affiliated with this site; competitor names are used for identification only.

author-avatar
Jane Smith

I’m Jane Smith, a senior content writer with over 15 years of experience in the packaging and printing industry. I specialize in writing about the latest trends, technologies, and best practices in packaging design, sustainability, and printing techniques. My goal is to help businesses understand complex printing processes and design solutions that enhance both product packaging and brand visibility.

Leave a Reply

Your email address will not be published. Required fields are marked *