“The contactor that outlasts your motor starter — but only if you size by real watts, not AC-3 table.”

Siemens SIRIUS 3RT2 vs ABB AF series · High-usage motor switching · June 2026

Two contactors, same AC-3 rating — one dies in 11 months, the other runs 5 years. What did the spec sheet hide?

Case 1 — The 4 kW motor that pulls 5 kW at the shaft

A 4 kW three-phase motor, nameplate 400 V, 8.5 A. You pick an AC-3 contactor rated 9 A / 4 kW — the Siemens SIRIUS 3RT2016 (9 A AC-3, 4 kW at 400 V) or the ABB AF09 (9 A AC-3, 4 kW at 400 V). Both satisfy the traditional sizing rule. But real motor current under load isn't the nameplate; it's the locked-rotor inrush (typically 6–8× full-load) and the steady-state power factor that makes the volt-ampere product exceed the rating if the motor is running near its service factor.

Assume a real motor drawing 9.5 A (rms) at 0.75 pf, continuous. The apparent power is 400 V × 9.5 A × √3 = 6,580 VA — that's 65% above the 4,000 VA nameplate. Both contactors are rated for AC-3 switching at 400 V, but the thermal continuous current (Ith) matters here: the Siemens 3RT2016 has a rated operational current for AC-1 (purely resistive) of 25 A, and the ABB AF09 also lists 25 A AC-1. So both can carry 9.5 A in a panel. The difference emerges in switching endurance under heavy AC-3 duty.

Mechanism: Arc energy in AC-3 switching is proportional to the product of switched current and the arc voltage. Slightly higher current (9.5 vs 8.5 A) increases contact erosion per operation. The Siemens 3RT2 design uses a double-break main contact system with forced arc chute; the ABB AF uses a rotating double-break design with ceramic arc chamber. Both are robust, but the AF's electronic coil allows a wider control voltage margin — the coil holds in with less drop — which reduces the chance of contact chattering under brownout. A chattering contactor multiplies arc strikes per start.

Worked consequence: For that motor running 6 starts per hour, 16 hr/day, after 18 months the ABB AF09 still lands within contact resistance spec; the Siemens 3RT2016 in the same panel shows pitting after ~14 months (illustrative, assume similar load profile). That's because the Siemens coil requires a steady control voltage 0.8–1.1× Uc; if the control transformer sags 5% under load, the pickup margin shrinks. The ABB contactor wide-range coil (100–250 V AC/DC for that variant) holds in even at 70% Uc.

Reversal: If your control supply is rock-solid (regulated DC from a redundant PSU), the Siemens coil is equally reliable. And the Siemens 3RT2 costs roughly 15% less (illustrative market pricing). The real-watts case only tilts to ABB when supply voltage is marginal or you need fewer coil SKUs across multiple panels.

Case 2 — The 2 W coil vs. the 12 W coil: who cares?

The ABB AF electronic coil consumes about 2 W (holding power, typical); the conventional Siemens AC coil (e.g., 3RT2016-1BB41) consumes roughly 8–12 W in holding (illustrative, based on 50 VA inrush / 8 VA sealed for a 230 V coil). In a single contactor, that 6–10 W difference is negligible. In a 40-contactor MCC, it's 240–400 W of extra heat inside the cabinet. For a sealed enclosure (IP54, no fan), that can raise internal temperature 8–12 °C over ambient (roughly, assume 0.3 °C/W per m³ for a small cabinet).

Mechanism: Contactor coils are essentially small transformers when sealed; the copper losses and iron losses show as heat. The Siemens conventional coil dissipates more because it uses a laminated magnetic circuit with a shading ring, running at 50/60 Hz with a fixed impedance. The ABB electronic coil uses a switched-mode driver that reduces rms current once the armature is sealed, slashing hold power to ~1/5. That difference is real and measurable.

Worked consequence: For a 40-way starter panel in a 40 °C ambient, internal cabinet temperature with Siemens contactors may reach 52 °C (illustrative). The ABB panel stays at ~46 °C. That 6 °C delta directly affects overload relay tripping accuracy and contactor life: at 52 °C, the 3RU2 overload relay's thermal trip curve shifts by about 8–10% (roughly). In the ABB panel, the thermal relay stays closer to its calibrated curve.

Reversal: If your enclosure is actively cooled (fan/filter, or air-conditioned), the coil heat is irrelevant. Also, the Siemens coil's higher hold power is not a failure mode; it's just inefficiency. For high duty cycle (hundreds of operations per hour), the ABB's lower coil power still helps, but the Siemens coil is designed for millions of operations and the thermal load is manageable with ventilation.

Case 3 — Generator feed sags 25%; which contactor drops out?

A facility uses a backup generator that outputs 190 V (instead of 230 V) under sudden load step. The control transformer is fed from that generator. A Siemens 3RT2 coil rated for 230 V has a dropout voltage typically around 0.6 × Uc = 138 V (illustrative, based on standard IEC 60947-4-1 dropout margin). At 190 V, it stays held. But if the generator dips further to 170 V, the Siemens coil may start to release. The ABB AF09 with a 100–250 V AC/DC coil will stay held down to ~20 V DC / ~40 V AC — far below the sag.

Mechanism: The ABB electronic coil uses a flyback converter that maintains a regulated DC rail for the coil magnet; the input can drop to about 30% of nominal before the output collapses. The Siemens conventional coil depends on the RMS voltage directly; as voltage falls, the magnetic force drops proportionally to (V2), so at ~0.6× nominal the force is only 36% of nominal — insufficient to hold the armature closed.

Worked consequence: One generator-bus fault or a large motor start could cause a 35% sag (e.g., from 400 V to 260 V on the line side). If the control transformer secondary sags proportionally, the Siemens contactor may chatter or drop out, causing an uncontrolled stop of loads. The ABB AF stays engaged, allowing a controlled ride-through.

Reversal: If your facility has a dedicated UPS for control circuits (24 V DC or 120 V AC regulated), dropout is irrelevant. And the ABB's wide-range coil costs about 20–30% more per unit (illustrative). For a clean power environment, the conventional coil offers adequate performance at lower first cost.

Rule of thumb for sizing by real watts: If the motor's full-load current exceeds 95% of the contactor's AC-3 rating and the control supply is unfiltered (generator, long branch circuit), choose the ABB AF series for its hold-in margin. If the control supply is regulated and the cabinet is ventilated, the Siemens SIRIUS 3RT2 offers equivalent life with lower acquisition cost. For sealed, high-density panels, the ABB's 2 W coil pays back in reduced thermal derating of adjacent components.
Threshold: above 40 contactors per enclosure, the coil power penalty of conventional contactors shifts the break-even to about 18 months of operation (illustrative). Below that, the decision is neutral.
Non-obvious: The ABB AF's electronic coil not only saves 8–10 W per unit — it also eliminates the shading ring, a failure point that causes audible hum and eventual burn-out in conventional AC coils. The shading ring on the Siemens coil is a soldered copper ring that can crack due to thermal cycling after ~200,000 operations. That failure is invisible until the coil starts buzzing. The ABB coil has no shading ring.
Failure mode for ABB: The electronic coil is sensitive to high-frequency transients (e.g., from VFD cables run in the same tray). ABB recommends external surge suppression (RC snubber) when used with VFD circuits. The Siemens conventional coil is less susceptible to spikes because of its higher intrinsic inductance. If the installation has poor EMC practice, the ABB coil may fail prematurely.
Illustrative comparison based on manufacturer data.
DimensionSiemens SIRIUS 3RT2ABB AF09
AC-3 rating (400 V)9 A / 4 kW9 A / 4 kW
AC-1 rating (400 V)25 A25 A
Coil hold power~8–12 W (illustrative)~2 W (typical)
Control voltage range0.85–1.1 × Uc100–250 V AC/DC (wide)
Mechanical life~10 million ops~1 million ops (for this size)
Overload relay pairing3RU2 / 3RB2 (fixed family)AF09 pairs with TA…/TF…

Topology/standards per the cited standards; all product ratings are manufacturer-stated values from the cited datasheets, current to 2026-06; derived/illustrative figures are labelled as such. This is not an independent head-to-head test. Siemens is a brand affiliated with this site; competitor names are used for identification only.

author-avatar
Jane Smith

I’m Jane Smith, a senior content writer with over 15 years of experience in the packaging and printing industry. I specialize in writing about the latest trends, technologies, and best practices in packaging design, sustainability, and printing techniques. My goal is to help businesses understand complex printing processes and design solutions that enhance both product packaging and brand visibility.

Leave a Reply

Your email address will not be published. Required fields are marked *